Logo Unex
Mini trunking 78 in LMP grey RAL 7035 colour

Technical specification

Mini trunking 78 in Logo grey RAL 7035 colour

Logo Unex

Description

Use

  • Trunking of small dimensions with external cover and surface mounting for power distribution and communication cables on walls and ceilings.
  • One to two compartments to separate circuits.

Installation

  • External lid and fittings are pressure mounted. Removable only with the aid of a tool.
  • Fittings in two pieces which assure a good retention of the cover in any mounting position. The internal one allows easy measuring of the cover and holds the cables and the external one hides the cut marks of the base and cover and assures protection degree IP4X.
  • 2m lengths and perforated base with 1 line of Ø4mm drill holes every 200mm for a faster assembly.

Design

  • Colour: Grey RAL 7035.
  • Homogeneity of colours between mini trunking and fittings.
  • It can be painted offering a wide range of possible surface treatments and their integration into the environment.

Mounting instructions

  • To fulfil the characteristics defined herein, the installation must be carried out in accordance with the manufacturer`s assembly instructions provided in the main product packaging and are also available on the website www.unex.net.

Quality Marks(1)

EN 50085-2-1:2006 + A1:2011
Licence nº: NF004_1175

EN 50085-2-1:2006 + A1:2011
Licence nº: 101833

ГOCT P 61084-1:2007 (GOST R 61084-1:2007)
POCC ES.AM05.H09265

UL 1565. CSA C22.2 No. 18.5.
Suitable for temperatures not exceeding 50ºC. Licence: E 75725 (M)

Approvals(1)

Rules for the Classification of Steel Ships
Type Approval Certificate nº 05116/I0 BV

Characteristics of Trunking system

Raw material
Mini trunkings
U23X (See technical data for raw material).
Fittings and accessories
U24X (See technical data for raw material).
Applications
Applications
Mini trunking system for indoor installations.
Silicone contents
Silicone free
<0,01%
Directive 2011/65/EU
RoHS Compliant
Compliant.
EN 50085-2-1:2006 + A1:2011
Minimum storage and transport temperature
-45ºC
Minimum installation and application temperature
-5ºC
Maximum application temperature
+60ºC
Resistance against mechanical impacts during mounting and use
  • Trunkings: 2 J at -5ºC
  • Fittings: 0,5 J at -5ºC
Resistance to flame propagation
Non-flame propagation.
Electrical continuity characteristic
Without electrical continuity characteristic.
Electrical insulating characteristic
With electrical insulating characteristic.
Protection degree assured by the enclosure
IP4X. Mounted on the wall or ceiling.
Retention of the system access cover
Cover removable only with the aid of a tool.
Electrically protective separation
Without internal protective separation.
Intended installation positions
Semi flush or surface mounted on the wall or ceiling.
Prevention of contact with liquids
Not declared.
Type
Type 2.
Rated Voltage
750 V
Protection against mechanical damage
IK07
EN 60695-2-11:2001
Glow-wire test
Severity degree: 960ºC

Characteristics of Trunking system

Raw material

Mini trunkings:
U23X (See technical data for raw material).
Fittings and accessories:
U24X (See technical data for raw material).

Applications

Applications:
Mini trunking system for indoor installations.

Silicone contents

Silicone free:
<0,01%

Directive 2011/65/EU

RoHS Compliant:
Compliant.

EN 50085-2-1:2006 + A1:2011

Minimum storage and transport temperature:
-45ºC
Minimum installation and application temperature:
-5ºC
Maximum application temperature:
+60ºC
Resistance against mechanical impacts during mounting and use:
  • Trunkings: 2 J at -5ºC
  • Fittings: 0,5 J at -5ºC
Resistance to flame propagation:
Non-flame propagation.
Electrical continuity characteristic:
Without electrical continuity characteristic.
Electrical insulating characteristic:
With electrical insulating characteristic.
Protection degree assured by the enclosure:
IP4X. Mounted on the wall or ceiling.
Retention of the system access cover:
Cover removable only with the aid of a tool.
Electrically protective separation:
Without internal protective separation.
Intended installation positions:
Semi flush or surface mounted on the wall or ceiling.
Prevention of contact with liquids:
Not declared.
Type:
Type 2.
Rated Voltage:
750 V
Protection against mechanical damage:
IK07

EN 60695-2-11:2001

Glow-wire test:
Severity degree: 960ºC

Compulsory regulations

European Directive 2014/35/EU
CE Marking
Conformity with standard EN 50085-2-1:2006+A1:2011.

Compulsory regulations

European Directive 2014/35/EU

CE Marking:
Conformity with standard EN 50085-2-1:2006+A1:2011.

Characteristics of U23X raw material

  • Base raw material: PVC.
  • Silicone contents: <0,01%.
  • Phthalate contents according to ASTM D2124-99:2004: <0,01%.
  • Dielectric strength according to EN 60243-1:2013: 18±5 kV/mm.
    Test sample thickness 2,5 mm.
  • Reaction to fire according to UNE 201010:2015: Classification: M1.
  • UL flammability tests on plastic materials according to ANSI/UL 94: 1990: Degree UL94: V0.
  • L.O.I. Oxygen index according to EN ISO 4589:1999 + A1:2006: (Concentration %) = 52±5.
  • Coefficient of linear expansion: 0,07 mm/°C m. (2)

Characteristics of U24X raw material

  • Base raw material: PVC.
  • Silicone contents: <0,01%. (3)
  • Phthalate contents according to ASTM D2124-99:2004: <0,01%. (3)
  • Dielectric strength: Insulating.
  • Reaction to fire s/UNE 201010:2015: Classification: M1
  • UL flammability tests on plastic materials according to ANSI/UL 94: 1990: Degree UL94: V0.
  • Coefficient of linear expansion: 0,07 mm/°C m. (2)

Notes

1. Except for new part numbers, which are under process of obtaining quality marks and approvals. See updated information of each part number on www.unex.net

2. All features marked are based on random tests of the material in the manufacture of our products. However, they only reflect the values accepted by the raw material manufacturers, which are provided only as information and guidance.

3. Detection limit for the analytical technique applied.

09/01/2024