Unex Trut 60®
Strut channel anchor system made of insulating material. It is possible to assemble structures such as H supports and corner supports of up to three levels.
Nuevo: No
Unex Trut 60®
Choose a product range
Unex Trut 60® halogen free
Choose a product range
for more information
Unex Trut 60® halogen free
Unex Trut 60®
Strut channel anchor system
Unex Trut 60® is a modular strut support system made of insulating material. This innovative solution is designed to provide maximum electrical safety and is positioned as the most reliable and efficient option on the market for a wide variety of industrial applications.
It is a versatile system, designed to adapt to different mounting configurations, whether wall, floor or ceiling mounted. It is compatible with our Insulating cable trays 66 and Insulating cable ladders 67.
It is possible to assemble structures such as H supports and corner supports of up to three levels, simplifying the installation process and reducing the need for additional parts, providing speed and less complexity in the execution of projects.
Benefits
of the insulating material
Insulating material: maximum electrical safety
- Electrical insulation is maintained over time.
- Increased protection for people and cables.
- Cost saving due to the ease of the installation, project management and maintenance.
Mounting types with Unex Trut® system
and Insulating cable tray 66
Direct wall mounting: 1 level
Horizontal support
Horizontal support in U48X insulating halogen free material.
Variable connectors - Unex Trut 60® system
Mounting with Insulating strut channels 60 and Insulating variable connectors 60 in tunnels and technical galleries with arched walls. To carry it out, the following must be taken into account:
- The maximum height by width of the Insulating cable tray 66 must be 100 x 300 mm.
- The bracket angle must be 45°.
- The strut channel perpendicular to the wall must be a maximum of 350 mm.
- Distance between supports at 40°C must be 1.5 m.
- Distance between supports at 60°C must be 1 m.
For correct assembly, follow the mounting instructions. See them here.
Strut channel
Strut channel in U48X insulating halogen free material.
Use metal screws to fix the support.
Maximum service temperature +60ºC.
Ceiling mounting: 1 level
Corner support with Insulating Strut Channel 60 - Unex Trut 60® system
Mounting with Insulating strut channels 60 and Insulating connectors 60. To carry it out, the following must be taken into account:
- The maximum height by width of the Insulating cable tray 66 must be 100 x 600 mm.
- The maximum height of the Insulating strut channel 60 must be 1105 mm.
- The width of the Corner support must be a maximum of 715 mm.
- Distance between supports at 40°C must be 1.5 m.
- Distance between supports at 60°C must be 1 m.
For correct assembly, follow the mounting instructions. See them here.
H support with Insulating Strut Channel 60 - Unex Trut 60® system
Mounting with Insulating strut channels 60 and Connectors 60. To carry it out, the following must be taken into account:
- The maximum height by width of the Insulating cable tray 66 must be 100 x 600 mm.
- The maximum height of the Insulating strut channel 60 must be 1105 mm.
- The width of the H support must be a maximum of 715 mm.
- Distance between supports at 40°C must be 1.5 m.
- Distance between supports at 60°C must be 1 m.
For correct assembly, follow the mounting instructions. See them here.
Reinforced pendant with horizontal support – Unex Trut 60® system
Mounting with Insulating strut channels 60, Insulating horizontal supports 60, Insulating connectors 60 and Insulating variable connectors 60. To carry it out, the following must be taken into account:
- The maximum height by width of the Insulating cable tray 66 must be 100 x 300 mm.
- The maximum height of the Insulating strut channel 60 must be 500 mm.
- Distance between supports at 40°C must be 1.5 m.
- Distance between supports at 60°C must be 1 m.
For correct assembly, follow the mounting instructions. See them here.
Pendant support with Insulating strut channel 60 – Unex Trut 60® system
Mounting with Insulating strut channels 60 and Insulating connectors 60. To carry it out, the following must be taken into account:
- The maximum height by width of the Insulating cable tray 66 must be 100 x 600 mm.
- The maximum height of the Insulating strut channel 60 must be 700 mm.
- Distance between supports at 40ºC must be 1.5 m.
- Distance between supports at 60ºC must be 1 m.
- The cable tray is fixed to the Strut channel using screw reference 66839-A4 or 66839-C6, never with the spring channel nut.
For correct assembly, follow the mounting instructions. See them here.
Strut channel
Insulating strut channel in U48X halogen free material.
Maximum service temperature +60ºC.
Ceiling mounting: several levels
Two-level corner support with Unex insulating strut channel 60 – Unex Trut 60® system
Mounting with Insulating Ssrut channels 60 and Insulating connectors 60.
To carry it out, the following must be taken into account:
- The maximum height by width of the Insulating cable tray 66 must be 100 x 600 mm.
- The maximum height of the Insulating strut channel 60 must be 1105 mm.
- The width of the Corner support must be a maximum of 715 mm.
- Distance between supports at 40°C must be 1.5 m.
- Distance between supports at 60°C must be 1 m.
For correct assembly, follow the mounting instructions. See them here.
Two-level H support with insulating strut channel 60 – Unex Trut 60® system
Mounting with Insulating strut channels 60 and Insulating connectors 60.
To carry it out, the following must be taken into account:
- The maximum height by width of the Insulating cable tray 66 must be 100 x 600 mm.
- The maximum height of the insulating strut channel 60 must be 1105 mm.
- The width of the H support must be a maximum of 715 mm.
- The distance between supports at 40°C must be 1.5 m.
- The distance between supports at 60°C must be 1 m.
For correct assembly, follow the mounting instructions. See them here.
Three-level corner support with insulating strut channel 60 – Unex Trut 60® system
Mounting with Insulating strut channels 60 and Insulating connectors 60.
To carry it out, the following must be taken into account:
- The maximum height by width of the Insulating cable tray 66 must be 100 x 600 mm.
- The maximum height of the insulating strut channel 60 must be 1105 mm.
- The width of the Corner support must be a maximum of 715 mm.
- The distance between supports at 40°C must be 1.5 m.
- The distance between supports at 60°C must be 1 m.
For correct assembly, follow the mounting instructions. See them here.
Three-level H support with insulating strut channel 60 – Unex Trut 60® system
Mounting with Insulating strut channels 60 and Insulating connectors 60.
To carry it out, the following must be taken into account:
- The maximum height by width of the Insulating cable tray 66 must be 100 x 600 mm.
- The maximum height of the insulating strut channel 60 must be 1105 mm.
- The width of the H support must be a maximum of 715 mm.
- The distance between supports at 40°C must be 1.5 m.
- The distance between supports at 60°C must be 1 m.
For correct assembly, follow the mounting instructions. See them here.
Floor mounting: 1 level
H support with insulating strut channel 60 – Unex Trut 60® system
Mounting with Insulating strut channels 60 and Insulating connectors 60. To carry it out, the following must be taken into account:
- The maximum height by width of the Insulating cable tray 66 must be 100 x 600 mm.
- The maximum height of the insulating strut channel 60 must be 1105 mm.
- The width of the H support must be a maximum of 715 mm.
- The distance between supports at 40°C must be 1.5 m.
- The distance between supports at 60°C must be 1 m.
For correct assembly, follow the mounting instructions. See them here.
Reinforced floor support with horizontal support – Unex Trut 60® system
Mounting with Insulating strut channels 60, Horizontal supports 60, Insulating connectors 60 and Insulating variable connectors 60. For this mounting, the following must be taken into account:
- The maximum height by width of the Insulating cable tray 66 must be 100 x 300 mm.
- The maximum height of the insulating strut channel 60 must be 500 mm.
- The distance between supports at 40°C must be 1.5 m.
- The distance between supports at 60°C must be 1 m.
For correct assembly, follow the mounting instructions. See them here.
Floor support with insulating strut channel 60 – Unex Trut 60® system
Mounting with Insulating strut channels 60 and Insulating connectors 60. For this mounting, the following must be taken into account:
- The maximum height by width of the Insulating cable tray 66 must be 100 x 300 mm.
- The maximum height of the insulating strut channel 60 must be 400 mm.
- The distance between supports at 40°C must be 1.5 m.
- The distance between supports at 60°C must be 1 m.
- The cable tray must be fixed to the strut channel using screw reference 66839-A4 or 66839-C6, never with the spring channel nut.
For correct assembly, follow the mounting instructions. See them here.
Rooftop support
Rooftop support in U48X insulating, halogen free material.
Cable trays must be fixed to the insulating rooftop supports by means of metal screws.
Floor mounting: several levels
Two-level H support with insulating strut channel 60 – Unex Trut 60® system
Mounting with Insulating strut channels 60 and Insulating connectors 60. For this mounting, the following must be taken into account:
- The maximum height by width of the Insulating cable tray 66 must be 100 x 600 mm.
- The maximum height of the insulating strut channel 60 must be 1105 mm.
- The width of the H support must be a maximum of 715 mm.
- The distance between supports at 40°C must be 1.5 m.
- The distance between supports at 60°C must be 1 m.
For correct assembly, follow the mounting instructions. See them here.
Corner support with insulating strut channel 60 – Unex Trut 60® system
Mounting with Insulating strut channels 60 and Insulating connectors 60. For this mounting, the following must be taken into account:
- The maximum height by width of the insulating cable tray 66 must be 100 x 600 mm.
- The maximum height of the insulating strut channel 60 must be 1105 mm.
- The width of the Corner support must be a maximum of 715 mm.
- The distance between supports at 40°C must be 1.5 m.
- The distance between supports at 60°C must be 1 m.
For correct assembly, follow the mounting instructions. See them here.
Three-level H support with insulating strut channel 60 – Unex Trut 60® system
Mounting with Insulating strut channels 60 and Insulating connectors 60. For this mounting, the following must be taken into account:
- The maximum height by width of the insulating cable tray 66 must be 100 x 600 mm.
- The maximum height of the insulating strut channel 60 must be 1105 mm.
- The width of the H support must be a maximum of 715 mm.
- The distance between supports at 40°C must be 1.5 m.
- The distance between supports at 60°C must be 1 m.
For correct assembly, follow the mounting instructions. See them here.
Mounting types with Unex Trut 60® system
and Insulating cable ladder 67
Direct wall mounting: 1 level
Horizontal support
Horizontal support in U48X insulating halogen free material.
Variable connectors - Unex Trut 60® system
Mounting with Insulating strut channels 60 and Insulating variable connectors 60 in tunnels and technical galleries with arched walls. To carry it out, the following must be taken into account:
- The maximum width of the Insulating cable ladder 67 must be 300 mm.
- The bracket angle must be 45°.
- The strut channel perpendicular to the wall must be a maximum of 350 mm.
- Distance between supports at 40°C must be 2 m for insulating cable ladders 85x300 mm in U23X and in U48X.
- Distance between supports at 40°C must be 3 m for insulating cable ladders 135x300 mm in U23X and in U48X.
- Distance between supports at 60°C must be 1.5 m for insulating cable ladders 85x300 mm in U23X.
- Distance between supports at 60°C must be 2 m for insulating cable ladders 135x300 mm in U23X and 85x300 mm in U48X.
- Distance between supports at 60°C must be 3 m for insulating cable ladders 135x300 mm in U48X.
For correct assembly, follow the mounting instructions. See them here.
Ceiling mounting: 1 level
Corner support with Insulating strut channel 60 – Unex Trut 60® system
Mounting with Insulating strut channels 60 and Insulating connectors 60. To carry it out, the following must be taken into account:
- The maximum width of the Insulating cable ladder 67 must be 600 mm.
- The maximum height of the Insulating strut channel 60 must be 1105 mm.
- The width of the Corner support must be a maximum of 715 mm.
- Distance between supports at 40°C must be 2 m for insulating cable ladders 85x600 mm in U23X and in U48X.
- Distance between supports at 40°C must be 3 m for insulating cable ladders 135x600 mm in U23X and in U48X.
- Distance between supports at 60°C must be 1.5 m for insulating cable ladders 85x600 mm in U23X.
- Distance between supports at 60°C must be 2 m for insulating cable ladders 135x600 mm in U23X and 85x600 mm in U48X.
- Distance between supports at 60°C must be 3 m for insulating cable ladders 135x600 mm in U48X.
For correct assembly, follow the mounting instructions. See them here.
H support with Insulating strut channel 60 – Unex Trut 60® system
Mounting with Insulating strut channels 60 and Insulating connectors 60. To carry it out, the following must be taken into account:
- The maximum width of the Insulating cable ladder 67 must be 600 mm.
- The maximum height of the Insulating strut channel 60 must be 1105 mm.
- The width of the H support must be a maximum of 715 mm.
- Distance between supports at 40°C must be 2 m for insulating cable ladders 85x600 mm in U23X and in U48X.
- Distance between supports at 40°C must be 3 m for insulating cable ladders 135x600 mm in U23X and in U48X.
- Distance between supports at 60°C must be 1.5 m for insulating cable ladders 85x600 mm in U23X.
- Distance between supports at 60°C must be 2 m for insulating cable ladders 135x600 mm in U23X and 85x600 mm in U48X.
- Distance between supports at 60°C must be 3 m for insulating cable ladders 135x600 mm in U48X.
For correct assembly, follow the mounting instructions. See them here.
Reinforced pendant with Horizontal support – Unex Trut 60® system
Mounting with Insulating strut channels 60, Insulating horizontal supports 60, Insulating connectors 60 and Insulating variable connectors 60. To carry it out, the following must be taken into account:
- The maximum width of the Insulating cable ladder 67 must be 300 mm.
- The maximum height of the Insulating strut channel 60 must be 500 mm.
- Distance between supports at 40°C must be 2 m.
- Distance between supports at 60°C must be 1.5 m for insulating cable ladders 85x300 mm in U23X.
- Distance between supports at 60°C must be 2 m for insulating cable ladders 135x300 mm in U23X and 85x300 mm and 135x300 mm in U48X.
For correct assembly, follow the mounting instructions. See them here.
Strut channel
Insulating strut channel in U48X halogen free material.
Maximum service temperature +60ºC.
Ceiling mounting: several levels
Two-level corner support with Insulating strut channel 60 – Unex Trut 60® system
Mounting with Insulating strut channels 60 and Insulating connectors 60. To carry it out, the following must be taken into account:
- The maximum width of the Insulating cable ladder 67 must be 600 mm.
- The maximum height of the Insulating strut channel 60 must be 1105 mm.
- The width of the Corner support must be a maximum of 715 mm.
- Distance between supports at 40°C must be 2 m for insulating cable ladders 85x600 mm in U23X and in U48X.
- Distance between supports at 40°C must be 3 m for insulating cable ladders 135x600 mm in U23X and in U48X.
- Distance between supports at 60°C must be 1.5 m for insulating cable ladders 85x600 mm in U23X.
- Distance between supports at 60°C must be 2 m for insulating cable ladders 135x600 mm in U23X and 85x600 mm in U48X.
- Distance between supports at 60°C must be 3 m for insulating cable ladders 135x600 mm in U48X.
For correct assembly, follow the mounting instructions. See them here.
Two-level H support with Insulating strut channel 60 – Unex Trut 60® system
Mounting with Insulating strut channels 60 and Insulating connectors 60. To carry it out, the following must be taken into account:
- The maximum width of the Insulating cable ladder 67 must be 600 mm.
- The maximum height of the Insulating strut channel 60 must be 1105 mm.
- The width of the H support must be a maximum of 715 mm.
- Distance between supports at 40°C must be 2 m for insulating cable ladders 85x600 mm in U23X and in U48X.
- Distance between supports at 40°C must be 3 m for insulating cable ladders 135x600 mm in U23X and in U48X.
- Distance between supports at 60°C must be 1.5 m for insulating cable ladders 85x600 mm in U23X.
- Distance between supports at 60°C must be 2 m for insulating cable ladders 135x600 mm in U23X and 85x600 mm in U48X.
- Distance between supports at 60°C must be 3 m for insulating cable ladders 135x600 mm in U48X.
For correct assembly, follow the mounting instructions. See them here.
Three-level corner support with Insulating strut channel 60 – Unex Trut 60® system
Mounting with Insulating strut channels 60 and Insulating connectors 60. To carry it out, the following must be taken into account:
- The maximum width of the Insulating cable ladder 67 must be 600 mm.
- The maximum height of the Insulating strut channel 60 must be 1105 mm.
- The width of the Corner support must be a maximum of 715 mm.
- Distance between supports at 40°C must be 2 m for insulating cable ladders 85x600 mm and 135x600 mm in U23X and in U48X.
- Distance between supports at 60°C must be 1.5 m for insulating cable ladders 85x600 mm in U23X.
- Distance between supports at 60°C must be 2 m for insulating cable ladders 135x600 mm in U23X and 85x600 mm and 135x600 mm in U48X.
For correct assembly, follow the mounting instructions. See them here.
Three-level H support with Insulating strut channel 60 – Unex Trut 60® system
Mounting with Insulating strut channels 60 and Insulating connectors 60. To carry it out, the following must be taken into account:
- The maximum width of the Insulating cable ladder 67 must be 600 mm.
- The maximum height of the Insulating strut channel 60 must be 1105 mm.
- The width of the H support must be a maximum of 715 mm.
- Distance between supports at 40°C must be 2 m.
- Distance between supports at 60°C must be 1.5 m for insulating cable ladders 85x600 mm in U23X.
- Distance between supports at 60°C must be 2 m for insulating cable ladders 135x600 mm in U23X and 85x600 mm and 135x600 mm in U48X.
For correct assembly, follow the mounting instructions. See them here.
Floor mounting: 1 level
Reinforced floor support with Horizontal support – Unex Trut 60® system
Mounting with Insulating strut channels 60, Insulating horizontal supports 60, Insulating connectors 60 and Insulating variable connectors 60. To carry it out, the following must be taken into account:
- The maximum width of the Insulating cable ladder 67 must be 300 mm.
- The maximum height of the Insulating strut channel 60 must be 500 mm.
- Distance between supports at 40°C must be 2 m.
- Distance between supports at 60°C must be 1.5 m for insulating cable ladders 85x300 mm in U23X.
- Distance between supports at 60°C must be 2 m for insulating cable ladders 135x300 mm in U23X and 85x300 mm and 135x300 mm in U48X.
For correct assembly, follow the mounting instructions. See them here.
Rooftop support
Rooftop support in U48X insulating, halogen free material.
Cable ladders must be fixed to the insulating rooftop supports by means of metal screws.
Floor mounting: several levels
Corner support with Insulating strut channel 60 – Unex Trut 60® system
Mounting with Insulating strut channels 60 and Insulating connectors 60. To carry it out, the following must be taken into account:
- The maximum width of the Insulating cable ladder 67 must be 600 mm.
- The maximum height of the Insulating strut channel 60 must be 1105 mm.
- The width of the Corner support must be a maximum of 715 mm.
- Distance between supports at 40°C must be 2 m for insulating cable ladders 85x600 mm in U23X and in U48X.
- Distance between supports at 40°C must be 3 m for insulating cable ladders 135x600 mm in U23X and in U48X.
- Distance between supports at 60°C must be 1.5 m for insulating cable ladders 85x600 mm in U23X.
- Distance between supports at 60°C must be 2 m for insulating cable ladders 135x600 mm in U23X and 85x600 mm in U48X.
- Distance between supports at 60°C must be 3 m for insulating cable ladders 135x600 mm in U48X.
For correct assembly, follow the mounting instructions. See them here.
H support with Insulating strut channel 60 – Unex Trut 60® system
Mounting with Insulating strut channels 60 and Insulating connectors 60. To carry it out, the following must be taken into account:
- The maximum width of the Insulating cable ladder 67 must be 600 mm.
- The maximum height of the Insulating strut channel 60 must be 1105 mm.
- The width of the H support must be a maximum of 715 mm.
- Distance between supports at 40°C must be 2 m for insulating cable ladders 85x600 mm in U23X and in U48X.
- Distance between supports at 40°C must be 3 m for insulating cable ladders 135x600 mm in U23X and in U48X.
- Distance between supports at 60°C must be 1.5 m for insulating cable ladders 85x600 mm in U23X.
- Distance between supports at 60°C must be 2 m for insulating cable ladders 135x600 mm in U23X and 85x600 mm in U48X.
- Distance between supports at 60°C must be 3 m for insulating cable ladders 135x600 mm in U48X.
For correct assembly, follow the mounting instructions. See them here.